The inspector was by today, looking at the work previously done and, thankfully, on the same permit, did a rough-in inspection. He was quite an agreeable fellow, addressing all my questions. So was Ryley, the electrician from Passey Electric. He found some deficiencies.
- Sep 11/2026 10:10AM (KEN) ROUGH IN: Range box and dryer box needs to have a second support. KF
- Sep 11/2026 10:11AM (KEN) ROUGH IN: Plug in kitchen area should be taken out on opposite side of panel. KF
- Sep 11/2026 10:13AM (KEN) ROUGH IN: Rough in of the upper unit was inspected with noted deficiencies. KF
- Sep 11/2026 10:15AM (KEN) ROUGH IN: 3 heat pumps and 2 baseboard heaters are being installed. KF
- Sep 11/2026 10:16AM (KEN) ROUGH IN: Fire alarm cable going downstairs to be completed. KF
- Sep 11/2026 10:05AM (KEN) ROUGH IN: DEFICIENCY: Rule 12-3010 (2) – Gangable boxes require a second support between studs ( could be factory boxes2 gang)
- Sep 11/2026 9:58AM (KEN) ROUGH IN: DEFICIENCY: Rule 12-516 – Protection plates required where wire is run less than 32 mm from edge of stud (throughout)
Along with that…
- The 15-15A space-saver breaker I put in for the split simplex outlet was wrong. Each circuit must be on a different phase. The reason being that the neutral wire would handle 15 amps for each circuit, amounting in 30 amps. I thought about this a few days ago and wondered how that worked. It never occurred to me that I need a 2-pole breaker with each circuit on a different phase. Again, Ryley is a helpful fellow.
Some of the work was done yesterday and some today.
So, here goes!





















